firmware
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revision | |||
| firmware [2022/03/15 16:50] – 142.97.231.36 | firmware [2025/01/28 15:24] (current) – external edit 127.0.0.1 | ||
|---|---|---|---|
| Line 4: | Line 4: | ||
| Requirement: | Requirement: | ||
| - | * BrewCMD | + | * {{ : |
| * Firmware file (*.bin) in the same directory as brewCMD.exe | * Firmware file (*.bin) in the same directory as brewCMD.exe | ||
| * Corresponding Brewer config file (*.cfg) brewcmd.exe | * Corresponding Brewer config file (*.cfg) brewcmd.exe | ||
| Line 13: | Line 13: | ||
| - Enter load mode: < | - Enter load mode: < | ||
| - Change the baud rate of load mode to 4800: < | - Change the baud rate of load mode to 4800: < | ||
| - | - Flash the *.bin firmware (I.E. V2R2C.bin) < | + | - Flash the *.bin firmware (I.E. For V2 (split boards) board **V2R2C.bin** or For V1 board **V1R3A.bin** |
| - BrewCMD will then display the following. < | - BrewCMD will then display the following. < | ||
| Writing file VR2R2C.bin to flash ....</ | Writing file VR2R2C.bin to flash ....</ | ||
| Line 21: | Line 21: | ||
| - Load the config into the brewer (I.E. brew190.cfg)< | - Load the config into the brewer (I.E. brew190.cfg)< | ||
| - Instruct the Brewer to use the new config < | - Instruct the Brewer to use the new config < | ||
| + | - Wait about 5 minutes or so until the micrometer has stopped moving (otherwise you will get qserial timeout) | ||
| - Save the config to the eeprom < | - Save the config to the eeprom < | ||
| - BrewCMD will display a number (4 or 32 when the firmware is just installed depending on the version of the board) | - BrewCMD will display a number (4 or 32 when the firmware is just installed depending on the version of the board) | ||
firmware.1647363013.txt.gz · Last modified: 2022/03/15 16:50 by 142.97.231.36